Yes, in fact the NESC requires the clearances it specifies to be maintained at the “worst case” sag and tension.
Clearances above ground must be maintained at 32°F with ice from the loading zone, 120°F, or greater than 120°F if so designed.
Clearances to buildings, mid-span clearances between power and communication cables, and other clearances in the span also have “worst case” sags specified. For example, some horizontal clearances may specify a temperature of 60°F with a wind pressure of 6 lb/ft².